SerVision MVG 400 System Guide
Resetting the Unit 155
Figure 147: Restart confirmation message
Restoring Factory Settings
If certain configuration settings are set incorrectly, or you forget their values, it may be
impossible to connect to the MVG 400 unit. For example, if you forget the username and
password required for configuring the unit, you will not be able to access the configuration
utility.
In this case, you can force all the configuration settings to be reset to their default values.
When you do this, the unit's IP and port are reset to the IP and port that appear on the sticker
on the underside of the unit (usually, the IP is 192.168.1.210 and the port is 9988), the
username and password required for access to the configuration utility are reset to
svuser
and
servconf respectively, and all other settings are reset to their original values. In
addition, all recorded video on the MVG 400 unit is erased.
Restoring the factory settings is accomplished by shorting two of the pins of the RS232/485
serial port connector together. To perform this procedure, it is best to use a jumper. Jumpers
are available at any electronics supply store.
Figure 148: Jumper
D
D
D
To reset the configuration settings to their factory values:
1. Disconnect the unit's power.
2. If anything is plugged into the RS232/485 connector (e.g., a PTZ camera controller or
the supplied RS232/485 adaptor), disconnect it from the port.